Permit: T05EL01876

Parcel: 129041840


Addresses:

121 S NORRIS AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/26/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/22/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) INSTALL 2ND GROUND ROD-6' MINIMUM APART
2) ID CIRCUIT BREAKERS
3) EXPOSE SPLICE IN WATER BOND CONDUCTOR
4) INSTALL RISER CLAMP PROPERLY