Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CLEAN PAINT AND OXIDATION OFF OF PIPES FOR BOND CLAMP TO MAKE CONTACT. COMPLETE ITEMS 2,4,7 OF PREVIOUS INSPECTION |
|
| 09/21/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE VERIFY NEW GROUNDING ELECTRODE SYSTEM, GAS AND WATER BONDS 2) TIGHTEN LOOSE FITTINGS 3) PROPERLY SUPPORT CONDUITS ABOVE AND BELOW PANEL 4) FULLY IDENTIFY UNDERGROUNDED CONDUCTORS 5) NM CABLE TO BE IN A NON FLEXIABLE RACEWAY 312.5 6) USE APPROVED SPLICES FOR COPPER TO ALUMINIUM 7) SECURE CABLE TO BACK OF PANEL |
|
| 09/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Lock up dogs in the yard.| 910* 1) NO ANSWER AT DOOR-PLEASE LOCK UP DOGS |