Permit: T05EL01840

Parcel: 134210100


Addresses:

141 S LANGLEY AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/02/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/28/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* PLEASE IDENTIFY CIRCUIT CONDUCTORS TO CHECK PHASING OF NEUTRALS AT JUNCTION BOX.
MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE 110.26
ENTRANCES ABOVE CURRENT CARRYING PARTS TO USE AN APPROVED SEALING DEVICE.
CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH CONDU??
PLEASE VERIFY HOME RUNS AS PER 310.15 (B)(2)(A)
A GAS BOND IS NEEDED 250.104
POOL BOND #8 TO BOND JUNCTION BOX PER 680.26 AND TIMER.
WHAT IS NEW # 12 NM CABLE AT POOL PUMP FOR? TEMP?