Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NOTE PERMIT WILL BE REQUIRED WHEN NEW A/C IS INSTALLED | |
| 09/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY PERMIT FOR NEW A/C 2) CHASE NIPPLE LISTED FOR ONLY PASSING THROUGH PARTITION. NO BONDING PROPERTIES. NOT A FITTING 3) TIGHTEN LOOSE LOCK NUT |
|
| 09/15/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE 110.26 2) WHAT IS EMPTY CONDUIT TO ROOF FOR ? 3) USE APPROVED FITTING WITH LB. CONDUIT OR CHASE NIPPLE NOT APPROVED 4) IDENTIFY GROUNDING CONDUCTORS AS PER 250.119 5) RISER HARDWARE TO BE 1/4" MINIMUM |