Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR INCREASE |
|
| 09/06/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) TIGHTEN LOOSE SEAL TITE FITTINGS 2) PLEASE VERIFY CIRCUITS FOR DOUBLED NEUTRAL AND GROUNDS TO CHECK PHASING 3) SHEET METAL SCREW NOT ALLOWED FOR GROUNDING |