Inspection History Details
Permit: T05EL01817
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO RECONNECT |
|
| 09/02/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FILL UNUSED OPENINGS IN BOX-FITTING MOST BE USED OR REMOVED AND SEALED, ALSO IN LIGHTS 2) PLEASE REMOVE NEON HIGH VOLTAGE WIRE BACK TO SERVICE 3) MAINTAIN CLEARANCE IN FRONT OF SERVICE EQUIPMENT 4) PERMANENT ADDRESS LABELING IS NEEDED FOR METAL TO IDENTIFY UNIT SPACES 5) FILL UNUSE OPENING IN PANEL COVERS-INSIDE AND OUTSIDE 6) REPLACE DAMAGED BOX COVER PLATE 7) SUPPORT RECEPTACLE BOX AND COVER 8) TERMINATE OR REMOVE UNSAFE CONDUCTORS 9) A L-11 CONTRACTOR TO PERFORM WORK 10) IF NEW WALLS ARE BUILT A PERMIT MAY BE NEEDED |