Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK CORRECTIONS | |
| 12/19/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ENERGIZE ALL SUB PANELS BOND ALL METAL PIPING SYSTEMS TO SERVICE NEC 250 104 ( B) BOND SEPARATELY DERIVED WATER PIPE TO SERVICE NEC 250 104 (A) TIGHTEN BONDING BUSHING IN CLUTTER PROVIDE ACCESS TO ROOF, SUBPANLES, AND SERVICE TIGHTEN GUTTER EQUIPMENT GROUND @ LUGS SECURE TO STRUCTURE OR BURY WATER BONDING CONDUCTOR GOIND TO WATER. |