Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/23/2005 | ELECTRIC - FINAL | Denied | 1. PLEASE COMPLETE PREVIOUS ITEMS #1,3,4. PERMIT IS REQUIRED TO ADD CIRCUIT AND COVER TO BE AS PER 406.8IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/20/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH LB OR TO BOX. 110.3 2) BOND FITTING TO LB 250.92 3) PLEASE ADD NEW CIRCUITS TO PERMIT - WELDER 4) COVER TO BE WEATHER PROOF WEATHER? OR NOT PLUGED IN 406.8 5) ANTI OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS 6) WHAT ARE 50A AND 30A BREAKERS FOR? |
|
| 09/19/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/18/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PLEASE LOCK UP DOBS? |