Permit: T05EL01808

Parcel: 125091390


Addresses:

2902 E 10TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01808

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/23/2005 ELECTRIC - FINAL Denied 1. PLEASE COMPLETE PREVIOUS ITEMS #1,3,4. PERMIT IS REQUIRED TO ADD CIRCUIT AND COVER TO BE AS PER 406.8IVRS - Inspection :
See detailed listing on site.| 999*
09/20/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH LB OR TO BOX. 110.3
2) BOND FITTING TO LB 250.92
3) PLEASE ADD NEW CIRCUITS TO PERMIT - WELDER
4) COVER TO BE WEATHER PROOF WEATHER? OR NOT PLUGED IN 406.8
5) ANTI OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS
6) WHAT ARE 50A AND 30A BREAKERS FOR?
09/19/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/18/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PLEASE LOCK UP DOBS?