Permit: T05EL01802

Parcel: 105131040

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/06/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
09/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM WRITTEN YESTERDAY RUN A JUMPER FROM THE GROUND TERMINAL TO PANEL ENCLOSURE TO CONNECT GROUND TO ENCLOSURE
08/31/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS PANEL IS A SUB-PANEL, THE SERVICE IS AT THE METER ENCLOSURE WHERE MAIN DISCONNECT IS, THEREFORE THE NEUTRALS AND GROUNDS NEED TO BE ISOLATED-REMOVE BAR CONNECTING BOTH. ALSO REMOVE GREEN SCREW ON NEUTRAL BAR AND CONNECT GROUNDING BAR WHERE ALL GROUNDS CONNECTED TO THE ENCLOSURE
2) SCHEDULE PANEL