Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 09/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM WRITTEN YESTERDAY RUN A JUMPER FROM THE GROUND TERMINAL TO PANEL ENCLOSURE TO CONNECT GROUND TO ENCLOSURE |
|
| 08/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THIS PANEL IS A SUB-PANEL, THE SERVICE IS AT THE METER ENCLOSURE WHERE MAIN DISCONNECT IS, THEREFORE THE NEUTRALS AND GROUNDS NEED TO BE ISOLATED-REMOVE BAR CONNECTING BOTH. ALSO REMOVE GREEN SCREW ON NEUTRAL BAR AND CONNECT GROUNDING BAR WHERE ALL GROUNDS CONNECTED TO THE ENCLOSURE 2) SCHEDULE PANEL |