Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/13/2005 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/09/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL 1/2" LOCKNUT AT EMT CONNECTOR IN PANEL
2) MULTI-WIRE CIRCUITS SHARING NEUTRAL NEED TO BE CONNECTED ON OPPOSITE PHASES
3) INSTALL METAL ADDRESS TAG-LABEL PER TEP AND IRC
4) RISER WIRES TO BE RATED FOR BOTH WATER AND SUNLIGHT RESISTANT
5) DRIVE RODS FLUSH OR BELOW FINISHED GRADE
6) BOND INTERIOR GAS PIPING
7) BOND INTERIOR WATER PIPING
8) INSTALL 2" ROOF JACK AT RISER
9) ALL #14 WIRE TO BE PROTECTED BY 15 AMP BREAKERS
10) NEED C-11 OR K-11 LICENSE ELECTRIC CONTRACTOR TO FINISH JOB
11) RISER WIRES TO BE SIZED PER 310-15 NEC