Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 09/09/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL 1/2" LOCKNUT AT EMT CONNECTOR IN PANEL 2) MULTI-WIRE CIRCUITS SHARING NEUTRAL NEED TO BE CONNECTED ON OPPOSITE PHASES 3) INSTALL METAL ADDRESS TAG-LABEL PER TEP AND IRC 4) RISER WIRES TO BE RATED FOR BOTH WATER AND SUNLIGHT RESISTANT 5) DRIVE RODS FLUSH OR BELOW FINISHED GRADE 6) BOND INTERIOR GAS PIPING 7) BOND INTERIOR WATER PIPING 8) INSTALL 2" ROOF JACK AT RISER 9) ALL #14 WIRE TO BE PROTECTED BY 15 AMP BREAKERS 10) NEED C-11 OR K-11 LICENSE ELECTRIC CONTRACTOR TO FINISH JOB 11) RISER WIRES TO BE SIZED PER 310-15 NEC |