Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR |
|
| 09/03/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE COMPLETE #4 OF PREVIOUS INSPECTION |
|
| 09/01/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND BUSHING ON BOTH SIDES OF SERVICE NIPPLE PER 250.92 2) PLEASE TIGHTEN GROUNDING ELECTRODE CONDUCTOR TERMINAL 3) SHEET METAL SCREWS NOT ALLOWED FOR GROUND/NEUTRAL BAR 4) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS INSTRUCTIONS |