Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/27/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*F CIRCUIT BREAKERS MUST ALL BE OF SAME MANUF. AS PANEL( MURRAY) TYPE. CIRCUIT MUST BE I.D |
|
| 09/13/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR INCREASE |
|
| 09/07/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KO ON TOP OF SERVICE PANEL TO BIG FOR FITTING, USE W/P HUB FOR TERMINATION. CAN SEE DAYLITE THRU FITTING 2) FOR 200 AMP UPGRADE, USE 2/0 MIN. CU. WIRE SIZE 3) J-BOX TO LEFT OF PANEL NEES HUB ALSO-SILICONE CAULKING NOT AN APPROVED METHOD FOR SEALING CONDUIT TERMINATION |
|
| 09/02/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) USE APPROVED WEATHER PROOF HUB FOR TOP CONDUIT TERMINATION |