Permit: T05EL01785

Parcel: 116123270


Addresses:

1438 W DELAWARE ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/30/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/27/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*F CIRCUIT BREAKERS MUST ALL BE OF SAME MANUF. AS PANEL( MURRAY) TYPE. CIRCUIT MUST BE I.D
09/13/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) OK TO CLEAR INCREASE
09/07/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KO ON TOP OF SERVICE PANEL TO BIG FOR FITTING, USE W/P HUB FOR TERMINATION. CAN SEE DAYLITE THRU FITTING
2) FOR 200 AMP UPGRADE, USE 2/0 MIN. CU. WIRE SIZE
3) J-BOX TO LEFT OF PANEL NEES HUB ALSO-SILICONE CAULKING NOT AN APPROVED METHOD FOR SEALING CONDUIT TERMINATION
09/02/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) USE APPROVED WEATHER PROOF HUB FOR TOP CONDUIT TERMINATION