Permit: T05EL01768

Parcel: 125041950


Addresses:

2404 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/15/2005 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
OK TO CLEAR - INC
CALL IN FOR FINAL AFTER TEP TIE IN
09/13/2005 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ITEMS ON NOTES LAST INSPECTION
09/10/2005 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1) FINISH DRIVING GROUND RODS-NEED 8' OF SOIL CONTACT
2) PLEASE VERIFY WATER AND GAS BONDING
3) FITTING SHOULDER TO SEAT TO BOX. LOCK NUT ON BACKWARDS
4) AN ADDRESS LABEL IS NEEDED
5) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG
6) LABEL BREAKER