Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* OK TO CLEAR - INC CALL IN FOR FINAL AFTER TEP TIE IN |
|
| 09/13/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ITEMS ON NOTES LAST INSPECTION |
|
| 09/10/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) FINISH DRIVING GROUND RODS-NEED 8' OF SOIL CONTACT 2) PLEASE VERIFY WATER AND GAS BONDING 3) FITTING SHOULDER TO SEAT TO BOX. LOCK NUT ON BACKWARDS 4) AN ADDRESS LABEL IS NEEDED 5) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG 6) LABEL BREAKER |