Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/22/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL BACK FOR FINAL 2) BLANK OFF ALL OPEN BREAKER SPACES 3) PLUG ALL HOLES IN OLD EQUIPMENT BOX 4) LABEL ALL CIRCUITS 5) LOCATE GAS/H20 BOND 6) ISOLATE GROUNDS/NEUTRALS AT OLD EQUIPMENT, REMOVE ANY GROUNDING AT NEUTRAL BAR |