Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL01693
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR RECONNECT |
|
08/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WAS HERE AT 11:20 AM NO ONE AROUND. KNOCKED LOUDLY SEVERAL TIMES, NO ANSWER. PLEASE RECALL AND LEAVE A MESSAGE. (RAY) |
|
08/18/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ROOM BY REAR DOOR-ROMEX WIRING HAS TO BE PHYSICALLY PROTECTED UP TO 8' 2) ROMEX ENTERING TOP OF PANEL TO HAVE PROPER FITTINGS 3) PANEL INSIDE REAR ROOM DOES NOT HAVE GROUND BAR CONNECTED TO ENCLOSURE 4) PVC CONDUIT TO PANEL IMPROPERLY INSTALLED 5) 30 AMP CB TO LARGE FOR #12 WIRE 6) THIS PERMIT NEEDS TO SHOW IF IT'S UNIT NUMBER 1 OR 2 7) OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN TO CORRECT WORK |