Permit: T05EL01693

Parcel: 115041480


Addresses:

1221 N TYNDALL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01693

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK TO CLEAR RECONNECT
08/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WAS HERE AT 11:20 AM NO ONE AROUND. KNOCKED LOUDLY SEVERAL TIMES, NO ANSWER. PLEASE RECALL AND LEAVE A MESSAGE. (RAY)
08/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ROOM BY REAR DOOR-ROMEX WIRING HAS TO BE PHYSICALLY PROTECTED UP TO 8'
2) ROMEX ENTERING TOP OF PANEL TO HAVE PROPER FITTINGS
3) PANEL INSIDE REAR ROOM DOES NOT HAVE GROUND BAR CONNECTED TO ENCLOSURE
4) PVC CONDUIT TO PANEL IMPROPERLY INSTALLED
5) 30 AMP CB TO LARGE FOR #12 WIRE
6) THIS PERMIT NEEDS TO SHOW IF IT'S UNIT NUMBER 1 OR 2
7) OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN TO CORRECT WORK