Permit: T05EL01676

Parcel: 125050080


Addresses:

2439 E 3RD ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/25/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
OK TO CLEAR WILL NOTIFY TEP
08/23/2005 ELECTRIC - SERVICE UPGRADE Partial Approval WHERE IS THE WATER AND GAS BOND ?
08/19/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) MAINTAIN SAFE WORKING CLEARANCES IN FRONT OF SERVICE (ROCKS)
2) RISER HARDWARE TO BE 1/4" MINIMUM
3) PLEASE VERIFY 2ND GROUND ROD AND BOND TO OTHER SERVICE AS PER 250.58
4) PLEASE PROVIDE ACCESS TO BACK YARD. GATES WILL NOT OPEN
5) CONDUCTORS NOT RUN AS PER PLANS. ALSO CANNOT PARALLEL NEUTRALS SMALLER THAN 1/0