Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 08/15/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPAIR INSUFFICIENT 2) SEAL ALL OPENINGS IN ELECTRICAL EQUIPMENT 3) SUPPORT ALL CONDUITS PROPERLY 4) SUPPORT GROUND WIRE TO WALL 5) ADD GROUND ROD TO GROUNDING SYSTEM AND DIRVE TO GRADE 6) INSTALL CIRCUIT BREAK BLANKS WHERE BREAKERS MISSING 7) REMOVE 2ND DISCONNECT AND INSTALL A WEATHER PROOF JUNCTION BOX-CIRCUITS ALREADY PROTECTED AT MAIN PANEL 8) ADD 2ND SUPPORT TO RISER 9) PROPERLY WIRE CIRCUIT ON WALL WHICH IS EXPOSED COMING OUT OF 1/2" LB 10) NEEDS MORE EXTENSIVE REPAIR AND CLEAN UP |