Permit: T05EL01667

Parcel: 11008247A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/18/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK FINAL
08/14/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. A DISCONNECTING MEANS IS NEEDED FOR MOTOR.
2. USED APPROVED TERMINAL ENDS FOR STANDARD WIRE.
3. SUPPORT CONDUIT AS PER CODE.
4. USE APPROVED FITTINGS WITH L.B. - EMT CONDUCTOR OR CHASE NIPPLE NOT APPROVED.
5. USE BREAKERS LISTED FOR USE BY MANUFACTURER AND USE AMPACITY AS PER PLANS.
6. A SEALING DEVICE FOR ENTRANCES ABOVE CURRENT CARRYING PARTS.