Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR |
|
| 08/17/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BONDING CONDUCTOR TO BOX TO BE SIZED PER 250.122 2) NEUTRAL IF INSTALLED AS MULTI-WIRE CIRCUITS TO HAVE UNGROUNDED CONDUCTORS IDENTIFYED AS CIRCUITS NUMBERS TO VERIFY PHASING OR RUN AS SINGLE LINE TO NEUTRALS LOADS 200.3 210.4 A AND C 3) GROUNDING EQUIPMENT CONDUCTORS TO BE SIZED AS PER 250.122 TO VERIFY EQUIPMENT LOADS. IF MULTI WIRE CIRCUITS 250.144 MAY APPLY ALSO 250.122.F.1 4) USE SPLICE CONNECTIONS LISTED FOR COPPER TO ALUMINIUM CONNECTIONS |
|
| 08/16/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND JUNCTION BOXES 2) NEUTRALS AND GROUNDS NOT TO BE DOUBLED OR TRIPPLED TO SERVICE-ONE FOR ONE OR VERIFY PHASING AND LOADS 3) PLEASE VERIFY GAS BOND |