Permit: T05EL01637

Parcel: 133350710


Addresses:

8760 E PATTERSON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/30/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK TO CLEAR
08/17/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) BONDING CONDUCTOR TO BOX TO BE SIZED PER 250.122
2) NEUTRAL IF INSTALLED AS MULTI-WIRE CIRCUITS TO HAVE UNGROUNDED CONDUCTORS IDENTIFYED AS CIRCUITS NUMBERS TO VERIFY PHASING OR RUN AS SINGLE LINE TO NEUTRALS LOADS 200.3 210.4 A AND C
3) GROUNDING EQUIPMENT CONDUCTORS TO BE SIZED AS PER 250.122 TO VERIFY EQUIPMENT LOADS. IF MULTI WIRE CIRCUITS 250.144 MAY APPLY ALSO 250.122.F.1
4) USE SPLICE CONNECTIONS LISTED FOR COPPER TO ALUMINIUM CONNECTIONS
08/16/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOND JUNCTION BOXES
2) NEUTRALS AND GROUNDS NOT TO BE DOUBLED OR TRIPPLED TO SERVICE-ONE FOR ONE OR VERIFY PHASING AND LOADS
3) PLEASE VERIFY GAS BOND