Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL01624
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*INTERIOR: WE HAVE GROUNDED RECEPTACLES ON UNGROUNDED CIRCUITS SMOKE DETECTORS IS NEEDED IN BEDROOMS-MY BE BATTERY OPERATED INTERIOR HAS EXCESS CLOTHING AND BOXES STACKED ON WALLS CANNOT REACH ALL RECEPTACLES |
|
| 09/26/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. FILL UNUSED OPENING IN BOTTOM OF PANEL. LABEL BREAKERS. RISER SUPPORTS TO BE 1/4" MINIMUM NO DRY WALL SCREWS. PLEASE ID NEUTRAL CONDUCTOR CLOSER TO WEATHER HEAD. UNIT LOCKED NEED ACCESS. | |
| 08/08/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE POST ADDRESS ON BLDG 2) SERVICE IN AN UNSAFE AND DETERIORATED CONDITION PLEASE UPGRADE 3) UNIT LOCKED NEED ACCESS 4) PVC WATER PIPE NOT ALLOWED FOR ELECTRICAL CONDUCTORS |