Permit: T05EL01619

Parcel: 11812065A


Addresses:

1250 S 4TH AV M1

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/22/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/20/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/19/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOND GAS PIPING ON CUSTOMER SIDE OF GAS METER, USE LISTED CLAMPS
2) ISOLATE GROUNDS AND NEUTRALS AT SUB PANELS
3) STRAP GROUND WIRE TO BLD
4) BOND GUTTER
5) GROUND LUGS LOOSE
6) USE EQUIP GROUNDS FOR GROUND BUSHING PER FEEDER RATING
7) TIE IN GROUNDS BETWEEN NEW AND EXIST. SERVICE