Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/19/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND GAS PIPING ON CUSTOMER SIDE OF GAS METER, USE LISTED CLAMPS 2) ISOLATE GROUNDS AND NEUTRALS AT SUB PANELS 3) STRAP GROUND WIRE TO BLD 4) BOND GUTTER 5) GROUND LUGS LOOSE 6) USE EQUIP GROUNDS FOR GROUND BUSHING PER FEEDER RATING 7) TIE IN GROUNDS BETWEEN NEW AND EXIST. SERVICE |