Permit: T05EL01597

Parcel: 107141120

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/20/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/05/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/27/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* #1 NOT COMPLETE ALL THE WAY
#1
#2 OK UP TO 6 THROWS
#3 OK NOT REQUIRED
#4 OK
5 OK
09/23/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920* NO ANSWER AT DOOR. COULD NOT OPEN GATE FROM OUTSIDE. RECALL INSPECTION.
08/19/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AN APPROVED WIRING METHOD AT BACK OF PANEL-METHOD NOT A SLEEVE. TERMINATE METHOD-ALSO FOAM IS COMBUSTIBLE LABELING TO BE PERMANENT
3) PLEASE COMPLETE ITEMS 1, 2, 4, 5 AND 6 OF PREVIOUS INSPECTION
08/15/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONDUIT TO BE AT 18" PER 300.5
2) A MAIN IS NEEDED AT 2ND STRUCTURE 225.30 AND 225.31
3) BOND NEUTRAL AND GROUND AT 2ND STRUCTURE 250.24
4) CONDUCTOR TO BE ENCLOSED IN A RACEWAY OR NIPPLE IN BACK OF PANEL. SINGLE CONDUCTORS NOT ALLOWED TO PASS THROUGH OPEN WALL
5) PLEASE LABEL 2ND PANEL
6) PLEASE VERIFY GAS AND WATER BONDS