Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR 2) NOTE TO HOME OWNER SUB-PANEL SI FED WITH 5O AMP WIRE, IT WAS ORIGINALLY FED WITH 60 AMP WIRE AND WAS PROTECTED AT 60 AMPS. YOU MAY WANT TO DISCUSS THIS WITH CONTRACTOR OR NOT |
|
| 08/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INTERIOR SUB-PANEL NEEDS A FULL SIZED INSULATED NEUTRAL AND SHOULD BE #6 AND ON A 60 AMP CIRCUIT BREAKER (ORIGINALLY FED FROM A 60 AMP SERVICE DISC. WITH 60 AMP FUSES) |
|
| 08/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE BOTH GROUND RODS FOR INSPECTION 2) BOND WATER PIPING TO ELECTRIC SERVICE 3) LABEL PANEL SCHEDULE 4) #6 THHN GOING INTO MASONRY WITHOUT CONDUIT THIS IS IN VIOLATION N.E.C. APPROVED WIRING METHODS 5) CLEAN PAINT OFF GAS BOND PIPE-CLAMP LOCATION |