Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/04/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/03/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) USE APPROVED FITTINGS AT SUB-PANEL AND PANEL 2) FULLY TERMINATE CONDUCTORS 3) AN ADDRESS LABEL IS NEEDED 4) PERMANENT MARKING FOR BREAKER 5) VERIFY ELECTRICAL CONTRACTOR 6) A GROUNDING ELECTRODE SYSTEM IS NEEDED-2 GROUND RODS 6' APART GAS AND WATER BONDS |