Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/18/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 11/17/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 11/09/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1) INDENTIFY NEUTRAL AT WEATHERHEAD BETTER 2) INSTALL FLASHING FOR MAST 3) REMOVE GROUND WIRE FROM MAST 4) NEED TWO GROUND RODS, ALSO NEED TO BOND GAS AND WATER PIPES 5) NEED MINIMUM 40 AMP CKT TO RANGE WITH INSULATED NEUTRAL (NOT GROUND) ALSO USE LISTED AL TO CU CONNECTORS 6) MARK PANEL DIRECTORY |