Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/12/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/07/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE IN FRON OF SERVICE 110.26 2) ANEW GROUNDING ELECTRODE SYSTEM IS NEEDED WITH WATER AND GAS BONDING 3) USE AN APPROVED FITTING WITH LB-CHASE NIPPLE NOT APPROVED 4) PROTECT CONDUCTORS IN COMBUSTIBLES 5) BREAKER TO BE LISTED FOR USE BY MANUFACTURE 6) RISER HARDWARE TO BE 1/4" MINIMUM 7) PLEASE LABEL BREAKER |