Permit: T05EL01560

Parcel: 11004342A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/18/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) OK TO CLEAR
2) DENNIS TO CHANGE COLOR TO ? FOR HIGH LEG 230.56
08/15/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) FINISH ITEMS #1, 2, 5, 6 AND 8 OF PREVIOUS INSPECTION
2) INSTALL NEUTRAL SIZED PER CODE
3) INSTALL TO A SAFE CONDITION SERVICE
08/11/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) USE PROPER TERMINAL LUG AT METER BASE FOR WIRE CONNECTIONS
2) ONLY ONE CONDUCTOR PER LUG AT DISCONNECT
3) CHASE NIPPLE NOT APPROVED FITTING
4) A PANEL WILL BE NEEDED AT THIS LOCATION. WE HAVE MULTIPLE CIRCUITS AND DEVICES
5) PLEASE VERIFY GROUNDING ELECTRODE SYSTEM
6) PROPERLY COVER CONDUCTORS PER 200.7
7) USE APPROVED AND LISTED JUNCTION BOX-NOT OLD STARTER CAN
8) HAVE DISCRIPTION CHANGED TO SERVICE UPGRADE
9) ADDRESS LABEL TO BE PERMANENT METAL LABEL