Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK TO CLEAR 2) DENNIS TO CHANGE COLOR TO ? FOR HIGH LEG 230.56 |
|
| 08/15/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FINISH ITEMS #1, 2, 5, 6 AND 8 OF PREVIOUS INSPECTION 2) INSTALL NEUTRAL SIZED PER CODE 3) INSTALL TO A SAFE CONDITION SERVICE |
|
| 08/11/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) USE PROPER TERMINAL LUG AT METER BASE FOR WIRE CONNECTIONS 2) ONLY ONE CONDUCTOR PER LUG AT DISCONNECT 3) CHASE NIPPLE NOT APPROVED FITTING 4) A PANEL WILL BE NEEDED AT THIS LOCATION. WE HAVE MULTIPLE CIRCUITS AND DEVICES 5) PLEASE VERIFY GROUNDING ELECTRODE SYSTEM 6) PROPERLY COVER CONDUCTORS PER 200.7 7) USE APPROVED AND LISTED JUNCTION BOX-NOT OLD STARTER CAN 8) HAVE DISCRIPTION CHANGED TO SERVICE UPGRADE 9) ADDRESS LABEL TO BE PERMANENT METAL LABEL |