Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/02/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEW SERVICE INSTALLED, ADD TO THIS PERMIT 2) BOND WATER AND GAS PIPING 3) 50 AMP CIRCUIT BREAKER ON #10 WIRE-CHANGE WIRE SIZE TO #8 OR BREAKER TO 30A 4) INSTALL SMOKE DETECTORS IN SLEEPING AREAS |
|
| 07/29/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER LINDA |