Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/02/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MUST HAVE 36" IN FRONT OF PANEL CLEAR DEDICATED SPACE PER 110.26 N.E.C. RELOCATE SERVICE PANEL OR FAUCETS IN FRONT OF SERVICE 2) DO NOT INSTALL LOAD CONDUCTORS BEHIND EXPOSED BUSS SHIELD AT TOP OF SERVICE PANEL. THIS AREA IS DEDICATED FOR LINE CONDUCTORS ONLY 3) CHASE NIPPLES NOT ALLOWED FOR TERMINATION AT BOTTOM OF PANEL USE CLOSE NIPPLES WITH LOCKNUTS BOTH SIDES OF ENCLOSURE |