Permit: T05EL01528

Parcel: 129064230


Addresses:

2328 E 21ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/03/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/02/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MUST HAVE 36" IN FRONT OF PANEL CLEAR DEDICATED SPACE PER 110.26 N.E.C. RELOCATE SERVICE PANEL OR FAUCETS IN FRONT OF SERVICE
2) DO NOT INSTALL LOAD CONDUCTORS BEHIND EXPOSED BUSS SHIELD AT TOP OF SERVICE PANEL. THIS AREA IS DEDICATED FOR LINE CONDUCTORS ONLY
3) CHASE NIPPLES NOT ALLOWED FOR TERMINATION AT BOTTOM OF PANEL USE CLOSE NIPPLES WITH LOCKNUTS BOTH SIDES OF ENCLOSURE