Permit: T05EL01526

Parcel: 12212075B


Addresses:

1304 N CATALINA AV


Inspection Status: Closed

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05EL01526

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Closed

Date Description Inspector Results Comments
03/28/2007 ELECTRIC - INTERMEDIATE Closed
08/05/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) RISER HARDWARE TO BE 1/4" MINIMUM
2) FINISH DRIVING GROUND RODS AND STRAP TO BLDG
3) NEED PERMANENT METAL ADDRESS LABEL
4) USE LISTED PVC GLUE, GLUE AND ? CONDUIT TO FITTINGS
5) 2ND SERVICE NOT FOR SUB-PANEL. ONLY SERVICE EQUIPMENT THIS IS NOT A SERVICE AFTER CHANGE
6) PLEASE VERIFY GAS BOND PERMIT FOR NEW A/C