Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05EL01458

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2005 ELECTRIC - INTERMEDIATE Approved
11/09/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1) TIGHTEN CLAMPS ON GROUND RODS
2) PROPERLY BOND GAS AND WATER PIPES
3) INSTALL MAX 15 AMP BREAKER ON 12 GA CLAD WIRING
4) BRING TO CODE OR REMOVE GFI AT SERVICE
5) SERVICE DROP TO BE APPROVED BY TEP