Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05EL01458
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | ELECTRIC - INTERMEDIATE | Approved | ||
| 11/09/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1) TIGHTEN CLAMPS ON GROUND RODS 2) PROPERLY BOND GAS AND WATER PIPES 3) INSTALL MAX 15 AMP BREAKER ON 12 GA CLAD WIRING 4) BRING TO CODE OR REMOVE GFI AT SERVICE 5) SERVICE DROP TO BE APPROVED BY TEP |