Permit: T05EL01434

Parcel: 120072040

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/28/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/26/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSTALL MISSING SCREWS TO COVERS OF SUB PANELS. CALL FOR FINALS WHEN DONE
2) SERVICE FOR #2 NEEDS TO BE ADDED TO THIS PERMIT
07/18/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALLATION OF 125 AMP LOAD CENTERS ON EXISTING 60 AMP METER BASES NOT ALLOWED. FOR SERVICE UPGRADE USE LISTED EQUIPMENT, DESIGNED AND LISTED FOR INSTALLATION
2) WIRING BETWEEN PANELS AT SERVICE NOT ALLOWED
3) LABELS MUST BE PER PERMIT #1 OR #2 NOT "A" AND "B"
4) SYSTEM NOT GROUNDED
5) VERIFY NAME AND PHONE NUMBER OF LICENSED CONTRACTOR DOING WORK-MUST BE LICENSED C-11