Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSTALL MISSING SCREWS TO COVERS OF SUB PANELS. CALL FOR FINALS WHEN DONE 2) SERVICE FOR #2 NEEDS TO BE ADDED TO THIS PERMIT |
|
| 07/18/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALLATION OF 125 AMP LOAD CENTERS ON EXISTING 60 AMP METER BASES NOT ALLOWED. FOR SERVICE UPGRADE USE LISTED EQUIPMENT, DESIGNED AND LISTED FOR INSTALLATION 2) WIRING BETWEEN PANELS AT SERVICE NOT ALLOWED 3) LABELS MUST BE PER PERMIT #1 OR #2 NOT "A" AND "B" 4) SYSTEM NOT GROUNDED 5) VERIFY NAME AND PHONE NUMBER OF LICENSED CONTRACTOR DOING WORK-MUST BE LICENSED C-11 |