Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH ITEMS 2, 3 AND 9 OF PREVIOUS INSPECTION 2) PLEASE MOVE WATER BOND TO INTERIOR SIDE OF DIE ELECTRIC UNION |
|
| 07/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A NEW GROUNDING ELECTRODE SYSTEM IS NEEDED GROUND RODS, GAS AND WATER BONDING PER 250 2) OPEN UP METER SCROCKET TO INSPECT CONNECTIONS AND BONDING PER 250.92 3) MAINTAIN CLEARANCES PER 230.24 4) PROTECT CONDUCTORS IN BACK OF PANEL 5) SEAL PANEL AND INTO HOUSE 6) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS LABEL 7) RISER STRAP TO BE SIZED FOR CONDUIT ALWO 1/4" MINIMUM HARDWARE 8) THIS IS A 200 AMP UPGRADE NOT 100 AMP 9) PLEASE VERIFY PERMITS FOR A/C AND WATER HEATER (NEW INSTALLS) |