Permit: T05EL01401

Parcel: 117091890


Addresses:

1141 S 7TH AV

Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/26/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE WIRING IN WALLS. FOR INSPECTION WIRING TO BE INSTALLED IN PROPER BOXES WHERE THEY TERMINATE OUT INTO WALLS (KIT).
2. LICENSED ELECTRICAL CONTRACTORS TO TAKE OVER.
3. CHASE OUT CIRCUITRY TO VERIFY PER PLAN.
4. WIRING NOT PER PLAN.
5. DOUBLE GANG SW BOXES OVER FILLED.
6. PERMITS FOR OTHER TRADES REQUIRED MECH, PLUMB.
7. OUTSIDE LIGHTS REAR MISSING - RECALL.
08/08/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PROVIDE 8' LADDER FOR ATTIC INSPECTION
2) EXPOSE WIRING IN MASONRY WALLS FOR INSPECTION, WIRING OR CABLE NEEDS TO BE 1 1/4" MINIMUM DEPTH INTO WALL
3) SOME CEILING BOXES NOT INSTALLED ?
4) PUSH IN TYPE BUSHINGS NOT ALLOWED FOR ROMEX TERMINATION UNLESS THEY CLAMP THE CABLE. USE ROMEX CLAMP TYPE CONNECTORS
08/04/2005 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled