Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
07/19/2005 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
07/15/2005 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/13/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :* 1) GROUNDING ELECTRODE SYSTEM TO BE RUN AS SUPPLEMENTAL NOT IN PARALED. 2) NO POWER IS CONNECTED TO SERVICE AT THIS TIME. 3) BOND JUNCTION BOX
07/12/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 2) GROUND RODS TO BE MINIMUM 6' APART. 3) SUPPORT BACK BOARD WITH HARDWARE OTHER THAN DRY WALL SCREWS 4) LABEL BREAKER. 5) FINISH CONNECTIONS FOR ???. 6) CONNECT WATER BOND TO INTERIOR SIDE OF UNIONS.