Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 07/15/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/13/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) GROUNDING ELECTRODE SYSTEM TO BE RUN AS SUPPLEMENTAL NOT IN PARALED. 2) NO POWER IS CONNECTED TO SERVICE AT THIS TIME. 3) BOND JUNCTION BOX | |
| 07/12/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26 2) GROUND RODS TO BE MINIMUM 6' APART. 3) SUPPORT BACK BOARD WITH HARDWARE OTHER THAN DRY WALL SCREWS 4) LABEL BREAKER. 5) FINISH CONNECTIONS FOR ???. 6) CONNECT WATER BOND TO INTERIOR SIDE OF UNIONS. |