Permit: T05EL01389

Parcel: 110070030


Addresses:

4250 E GLENN ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/02/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO WORK PROGRESS - EXPLAINED HOLD DOWN OR MAIN KIT
05/30/2006 ELECTRIC - FINAL Cancelled CANCELLED PER (OWNER) VIVIANA #207-3067
05/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY OFFICE
01/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
NO WORK PROGRESS THIS IS THE 5TH TRIP TO INSPECT MAIN BREAKER - A REFEE HAS BEEN ASSESSED PER ADMINISTRATIVE CODES.
11/21/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*MISSING RETAINING CLIP ON SUB PANEL BACK FED BREAKER 100A
11/18/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*NOT READY 10:30 AM
1. CLIP HOLD DOWN FOR BACK FED BREAKER AT MAIN SERIVCE FOR HOUSE SUBPANEL
REMOVE TEMP RECEPTACLE UNDER SERVICE.
11/10/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*PLEASE VERIFY MANUFACTURERS HOLD DOWN # 1 7-15-05
LABEL PANEL ON OUTSIDE OF COVER
REMOVE TEMP SERVICE OUTLET AND SELA UNUSED OPENING
07/15/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*