Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 07/15/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 07/14/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE FITTINGS AND SUPPORT CONDUIT 2) WIRING METHOD TO BE FOR WEATHER PROOF LOCATION 3) A NEW GROUNDING ELECTRODE SYSTEM IS NEEDED AT 2ND STRUCTURE AND STRAPED TO STRUCTURE 4) CONDUIT TO HAVE 18" OF COVER 5) A MAIN BREAKER IS NEEDED AT 2ND STRUCTURE 225.31 AND 32 6) FILL UNUSED OPENING AT BACK OF PANEL WITH NON COMBUSTIBLE MATERIAL 7) BOND AT CONCENTRICS FOR FITTING 8) LABEL BREAKERS 9) RISER HARDWARE TO BE 1/4" MINIMUM 10) BOND GAS AND WATER |