Permit: T05EL01389

Parcel: 110070030


Addresses:

4250 E GLENN ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
07/23/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
07/15/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/14/2005 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS AND SUPPORT CONDUIT
2) WIRING METHOD TO BE FOR WEATHER PROOF LOCATION
3) A NEW GROUNDING ELECTRODE SYSTEM IS NEEDED AT 2ND STRUCTURE AND STRAPED TO STRUCTURE
4) CONDUIT TO HAVE 18" OF COVER
5) A MAIN BREAKER IS NEEDED AT 2ND STRUCTURE 225.31 AND 32
6) FILL UNUSED OPENING AT BACK OF PANEL WITH NON COMBUSTIBLE MATERIAL
7) BOND AT CONCENTRICS FOR FITTING
8) LABEL BREAKERS
9) RISER HARDWARE TO BE 1/4" MINIMUM
10) BOND GAS AND WATER