Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) EXPOSED GROUND RODS FOR INSPECTION. 2) BOND WATER & GAS PIPING. 3) CHASE NIPPLE ON 1" LB TERMINATION INTO PANEL NOT ALLOWED USED CLOSED NIPPLE WITH LOCKNUTS BOTH SIDES OF ENCLOSURE. 4) BOND BUSHING REQUIED ON NIPPLE BETWEEN PANEL & METER BASE. 5) CIRCUTI BREAKERS MUST BE OF SAME MANUF AS PANEL. |