Permit: T05EL01370

Parcel: 138233620


Addresses:

832 W BAFFIN DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/13/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* 1) EXPOSED GROUND RODS FOR INSPECTION. 2) BOND WATER & GAS PIPING. 3) CHASE NIPPLE ON 1" LB TERMINATION INTO PANEL NOT ALLOWED USED CLOSED NIPPLE WITH LOCKNUTS BOTH SIDES OF ENCLOSURE. 4) BOND BUSHING REQUIED ON NIPPLE BETWEEN PANEL & METER BASE. 5) CIRCUTI BREAKERS MUST BE OF SAME MANUF AS PANEL.