Permit: T05EL01353

Parcel: 11521147A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01353

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/07/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. IN SERVICE PANEL CANNOT HAVE 2 WIRES. TERMINATED IN 1 BREAKER, ALSO BREAKER IS 30 AMP AND ONE OF THE WIRES IS # 12 GOOD FOR 20 AMP ONL Y. 2. ELECTRICAL BOXES OUTSIDE NEED TO BE RESUPPORTED AND CONDUITS RESTRAPPED. 3. OUTSIDE FRONT FIXTURES BY GARAGE ENTRANCE CANNOT HAVE OPEN SPLICES EXPOSED. 4. WIRING INSIDE ABOVE GARAGE DOOR TO BE CORRECTED & PROTECTED UNDER 8'. EVERYTHING ELSE OK. PLEASE CORRECT & RECALL. 5. PVC CONDUIT AT SIDE OF SERVICE TO BE STRAPPED.