Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) OK TO CLEAR INCREASE |
|
| 08/05/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NO SPLICES ON GROUND ELECTRODE CONDUCTOR 2) BOND WATER PIPING 3) JUNCTION BOX NOT RATED FOR OUTDOOR USE |
|
| 08/04/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCK UP DOG - RECALL INSPECTION -- NO ANSWER AT FRONT DOOR. |