Permit: T05EL01335


Addresses:

825 W CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01335

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2007 ELECTRIC - FINAL Approved
11/17/2006 ELECTRIC - FINAL Partial Approval AT FINAL WILL NEED TO SEE SPLICES AT POLES, OPEN PULL BOXES FOR VERIFICATION OF APPROVED METHOD
GFI PROTECTED RECEPTACLES
WILL NOTIFY TEP FOR POWER CLEARANCE
11/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SPLICING AT J-BOXES MUST BE APPROVED FOR UNDERGROUND, WIRE NUTS WITH BLACK OR FRICTION TAPE INSUFFICIENT.

PLEASE CHECK REST OF J-BOXES AND USE APPROVED OR LISTED METHOD.

2. IF FINAL IS BEING REQUESTED PLEASE LEAVE A COPY OF APPROVED PLANS AND LEAVE J-BOXES SO COVER CAN BE REMOVED.
3. PERMANENTLY MARK ALL CIR'S ON PNL.
10/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
PARTIAL INSPECTION ONLY
1. BOND ALL SERVICE RACEWAYS -- NEC 259.92
2. BOND NEUTRAL TO SERVICE ENCLOSURE -- NEC 250.24 B
3. CABINET ASSEMBLY REQUIRES A LISTING -- NEC 110.3
4. PROVIDE PROTECTION TO LIVE PARTS -- NEC 110.27
5. RACEWAYS NEED TO BE MADE COMPLETE (BRANCH CKTS) NEC 300.15, 16, 18
6. HAVE OBJECTIONABLE CURRENT ON BOND CONDUCTOR
NEC 250.6

JERRY 955-0205