Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05EL01314

Parcel: 117060660


Addresses:

228 N 4TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01314

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/20/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK TO CLEAR INCREASE
07/13/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) PERMIT IS FOR REPLACE 200 AMP PANEL. WE HAVE A NEW SUB PANEL, NEW CIRCUIT TO DRYER NEED TO BE ADDED TO PERMIT. 2) REMOVE PIPE STUBBED UP INFRONT OF SERVICE OR CAP OFF AT OR BELOW GRADE SUBPANEL. 3) NEUTRAL CONDUCTOR NOT BE SPLIT. 4) BREAKER TO BE LISTED FOR USE BY MANUFACTURE 5) PLEASE LABEL PANEL ON OUTSIDE COVER.
07/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) PLEASE ALL NEW CIRCUITS TO PERMIT 2) BOND ALL GAS UNITS. 3) CHASE NIPPLES NOT AN APPROVED FITTING WITH LB. 4) BOND SERVICE NIPPLE BOTH SIDES PER 250.92. 5) SEALING DEVICE NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 6) CONDUCTORS AT WEATHER HEAD TO BE SUNLIGHT RESISTANT. 7) STRAP GROUND CONDUCTORS WITH UV RATED STRAPS. 8) SUPPORT CONDUITS AS PER CODE. 9) TIGHTEN LOOSE FITTINGS. 10) LIGHT FIXTURE TO HAVE A BOX FOR CONVECTIONS TO LIGHT. 11) RECEPTACLE COVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED IN 408.6 12) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 110.26