Permit: T05EL01306

Parcel: 114462100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/21/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
07/20/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) USE FITTING LISTED FOR APPLICATION
2) CONDUIT NOT TO HAVE MORE THAN 360 DEGREE IN A RUN
3) MULTIPLE TERMINATIONS AT GROUND LUGS
4) HIGH LEG PHASING TO BE ON SAME PHASE THROUGH OUT ALL ELECTRICAL CONNECTIONS. ALL HIGH LEG PHASES TO BE MARKED. ALSO EQUIPMENT TO BE LABELED
5) PLEASE VERIFY LISTING LABEL FOR CAR WASH EQUIPMENT