Permit: T05EL01272

Parcel: 137040620


Addresses:

5382 S NOGALES HY

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
07/05/2005 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/28/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) COOLER SWITCHES/BOXES NEED TO BE SUPPORTED TO STRUCTURE CANNOT USE FITTINGS FOR SOLE SUPPORT.
06/27/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. NEED WEATHER PROOF LOUVERS ON OUTSIDE RECEPTACLES 2. INSIDE PANEL-SEAL TOP HOLE. 3. USE SAME TYPE BREAKERS A PANEL. 4. PROPERLY SIZE BREAKERS TO CIRCUITS. 5. COOLER SWITCHES TO BE PROPERLY MOUNTED 6. TIME CLOCK TO BE SUPPORTED. 7. COOLER SWITCHES ON 2ND PANEL EAST IMPROPERLY SUPPORTED. 8. SWITCH AT FRONT SALES AREA NEEDS EXTENSION RING & COVER. 9. REMOVE EXTENSION WIRING AT BOTTOM OF STAIRS. 10. SECURE ALL EXPOSED MC CABLE BY PANELS AND RECEPTACLES.