Permit: T05EL01263


Addresses:

3113 E 1ST ST #105

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
01/30/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE THREADED CONNECTIONS FOR GROUND LUGS (OR NUT & BOLT)
2. BOND WIRE TO BE SIZED PER NEC 250.66
3. SECURE EQUIPMENT TO WALL
4. MAKE SURE ALL LUGS AND BUSHINGS ARE TIGHT
01/25/2006 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE ALL PANELS AND GUTTERS OPEN FOR INSPECTION
2) PROVIDE LADDER AND PLANS FOR INSPECTION