Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/13/2005 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 07/06/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* 207-0654 NO ANS 10:30 AM. 1) SUBPANEL HAS NEUTRALS CONNECTED TO GROUND BAR, GROUNDS CONNECTED TO NEUTRAL BAR. 2. DRYER OULET NEEDS COVER. 3. SMOKE DETECTORS IF INSTALLED ON CEILING TO BE 18" AWAY FROM CORNERS. 4. HALL SD NOT SOUNDING ALARM. SERVICE. 1. NEED A PERMIT FOR SERVICE UPGRADE. 2. GROUNDING OF SERVICE REQUIRES 2-8' GROUND RODS 6' APART OR MORE & WATER AND GAS LINE BOND CONNECTED. |