Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05EL01257

Parcel: 106122890


Addresses:

1546 W MOHAVE RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/13/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/06/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 207-0654 NO ANS 10:30 AM. 1) SUBPANEL HAS NEUTRALS CONNECTED TO GROUND BAR, GROUNDS CONNECTED TO NEUTRAL BAR. 2. DRYER OULET NEEDS COVER. 3. SMOKE DETECTORS IF INSTALLED ON CEILING TO BE 18" AWAY FROM CORNERS. 4. HALL SD NOT SOUNDING ALARM. SERVICE. 1. NEED A PERMIT FOR SERVICE UPGRADE. 2. GROUNDING OF SERVICE REQUIRES 2-8' GROUND RODS 6' APART OR MORE & WATER AND GAS LINE BOND CONNECTED.