Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE GROUND RODS 2) INSTALL LISTED MAST BRACING, CANNOT USE SMASHED EMT 3) SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL |