Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/06/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* OK TO CLEAR INC #1 1) INSTALL ADDRESS LABEL ON SERVICE MUST BE PERMANENT NO MARKING PEN. 2) INDICATE PVC PLUMBING SYSTEM INSIDE PANEL DOOR, NOT ON PAPER NOTE. CALL FOR FINAL INSPECTION AFTER TEP CONNECT | |
| 06/28/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) 2 GROUND RODS REQUIRED 6' MIN. APART. 2) BOND WATER & GAS PIPING. 3) RISER CONDUIT SUPPORT REQUIRED WITHIN 3' OF TERMINATION AT SERVICE ENCLOSURE. 4) STRAP # 4 BARE TO WALL. 5) SUPPORT 3/4" PVC CONDUIT. |