Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T05EL01219
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
08/15/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/05/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AN ELECTRICAL LICENSED CONTRACTOR IS REQUIRED BY REGISTRAR OF CONTRACTORS 2) PVC SCHEDULE 40 CANNOT BE USED ABOVE GRADE 3) PVC SCHEDULE 40 MUST BE BURRIED 18" DEEP 4) SERVICES TO BE LABELED 5) GROUND RODS NOT TO BE BENT |