Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE LABEL BREAKERS AND RECALL AFTER POWER IS ON. | |
| 06/15/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STRAP GROUNDING ELECTRODE TO STRUCTURE. 2) PLEASE CLEAN?? FROM GAS BOND. 3) CHASE NIPPLE NOT AN APPROVED FITTING. 4) PLEASE LABEL BREAKERS. 5) ANTIOXIDE COMPOUND NEEDED FOR ALUMINIUM CONDUCTORS. 6) SO CORD NOT ALLOWED FOR PERMANENT WIRING METHOD. 7) SEAL ENTRANCES WITH AN APPROVED DEVICE ABOVE CURRENT CARRING PARTS. |